Haws 6429 Installation Instructions & Guidance

The Haws 6429 is a screw-in replacement filter cartridge for Brita® Hydration Station™ models 2000S and 2000SMS, and it can be changed without shutting off the water supply. We recommend having facility maintenance staff or a qualified technician handle the replacement.

Key Installation Requirements:

  • A Brita® Hydration Station™ model 2000S or 2000SMS
  • The hex key supplied with the unit, or a long, small slotted screwdriver, to open the hinged panel
  • Access to the filter head and cartridge wiring inside the unit
  • About 5 gallons of water run through the unit after installation to flush the new cartridge
  • Water shutoff only if the filter head will be left without a cartridge for a long period

Important Notes Before Installing the 6429:

  • The filter status LED blinks yellow when about 10% of filter life remains, so that's a good time to have a replacement 6429 on hand.
  • When the LED flashes red, the unit will not dispense water until the filter is replaced.
  • Opening the hinged panel cuts power to the sensor and solenoid valve, which prevents accidental activation during service.
  • The 6429 does not fit every Brita® Hydration Station™. Models 2000 and 2000SM use the Haws 6424, model 2520 uses the Haws 6441, and Hydration By Haws™ versions use the Haws 6423.
  • Always refer to the official Haws 6429 Spec Sheet for capacity, certification and performance details.

Basic Installation Overview:

  1. Open the unit: slide the hex key into the notch, press firmly to release the internal spring latch, and pull open the hinged panel.
  2. Disconnect the old cartridge's wiring and unscrew the old cartridge from the filter head.
  3. Screw the new 6429 cartridge firmly into the filter head and connect its wiring.
  4. Close the hinged panel. The filter status LED should flash green after closing and while water is dispensing.
  5. Run about 5 gallons of water through the system to flush out loose carbon fines and trapped air.
  6. Open the unit to check for leaks, then close it. If the LED still shows red, cycle the power off and on by opening and closing the panel.

For complete step-by-step instructions, download the official Brita® Hydration Station™ Owner's Manual


Want to Order the 6429 or Get a Custom Quote?

Shop now at BottleFillingStations.com